Nutter Tools
Nutter Tools

A free toolbox that runs in your browser. A tool for every job.

Your files never leave your device

Images

  • Convert images
  • Compress images
  • Resize images
  • Crop
  • Watermark

PDF & files

  • Merge PDFs
  • Split a PDF
  • Images to PDF
  • PDF to images
  • Remove photo location

Video & audio

  • Compress video
  • Convert video
  • Video to GIF
  • Convert audio
  • Trim audio

Everyday

  • QR codes
  • Passwords
  • Time zones
  • Unit converter
  • Word count
  • Webcam test

Developer

  • JSON formatter
  • Base64
  • Regex tester
  • Hashes
  • JWT decoder

Site

  • About
  • Contact
  • Settings
  • Privacy
  • Terms
  • Site map
  • llms.txt

Everyday

  • Images
  • Video
  • Audio
  • PDF & files
  • Text
  • QR codes
  • Units & math
  • Time & dates
  • Color
  • Passwords & IDs
  • Device tests
  • Sun & moon

For developers

  • JSON
  • Encoding
  • Regex & cron
  • Web & auth
  • Hashing & encryption
  • Config files
  • Network
  • Browser
  • AI
  • Fake data
© Nutter Toolsnutter.tools
  1. Home
  2. Units & math
  3. Star-Delta starter
Your files stay on your device

Star-Delta starter

Size the three contactors and overload relay for a star delta starter, with winding currents and start values against DOL.

This tool is in beta

Still being tested. If a result looks wrong, tell us.

Report a problem

Enter the nameplate full-load current to size the starter.

The sizing rules: main and delta contactors both carry winding current, 57.7 percent of the line figure, so they are sized at 0.58 times full-load current. The star contactor conducts only during starting and is conventionally sized at 33 percent. The overload relay setting here assumes it sits in the windings, where it reads phase current of 0.58 times nameplate; a relay ahead of the starter reads line current and needs the full nameplate figure. In star, each winding sees V over √3, so starting current and starting torque are exactly one third of the direct-on-line values. Star-delta suits loads that start light; a compressor under load or a conveyor under belt tension may never reach changeover speed in star.

Motor nameplate

More settings▾

Times full load, usually 6. Leave it empty for the conventional 6 and the result says it fell back.