Nutter Tools
Nutter Tools

A free toolbox that runs in your browser. A tool for every job.

Your files never leave your device

Images

  • Convert images
  • Compress images
  • Resize images
  • Crop
  • Watermark

PDF & files

  • Merge PDFs
  • Split a PDF
  • Images to PDF
  • PDF to images
  • Remove photo location

Video & audio

  • Compress video
  • Convert video
  • Video to GIF
  • Convert audio
  • Trim audio

Everyday

  • QR codes
  • Passwords
  • Time zones
  • Unit converter
  • Word count
  • Webcam test

Developer

  • JSON formatter
  • Base64
  • Regex tester
  • Hashes
  • JWT decoder

Site

  • About
  • Contact
  • Settings
  • Privacy
  • Terms
  • Site map
  • llms.txt

Everyday

  • Images
  • Video
  • Audio
  • PDF & files
  • Text
  • QR codes
  • Units & math
  • Time & dates
  • Color
  • Passwords & IDs
  • Device tests
  • Sun & moon

For developers

  • JSON
  • Encoding
  • Regex & cron
  • Web & auth
  • Hashing & encryption
  • Config files
  • Network
  • Browser
  • AI
  • Fake data
© Nutter Toolsnutter.tools
  1. Home
  2. Units & math
  3. Power factor correction
Your files stay on your device

Power factor correction

Size the capacitor bank that moves a load to a target power factor, with per-phase capacitance, released capacity, and bank steps.

This tool is in beta

Still being tested. If a result looks wrong, tell us.

Report a problem

Enter the load and both power factors to size the bank.

The formulas: Qc = kW × (tan(arccos pf₁) − tan(arccos pf₂)), kVA = kW ÷ pf, capacitance per phase from Q = 2πfCV² with a factor of 3 for the delta bank, line current falling by pf₁/pf₂ and I²R cable losses by its square. The kW never changes; only kVA and current drop. This is displacement power factor for a balanced load: harmonic distortion is not measured and a plain bank cannot fix it. A step suggestion from this page is a starting point, not a design; have a qualified engineer verify the installation against IEC 60831-1, IEC 61921, and IEEE 519.

Load and supply

SupplyAssumed balanced across phases
More settings▾

Up to 24 steps, separated by commas. The table below switches them in one at a time and shows the power factor after each. The transformer rating is optional; with it you get the released capacity.

Numbers stay within ±1,000,000. The target must sit above the present power factor: lowering it would take inductance, and this tool only sizes capacitors.