Nutter Tools
Nutter Tools

A free toolbox that runs in your browser. A tool for every job.

Your files never leave your device

Images

  • Convert images
  • Compress images
  • Resize images
  • Crop
  • Watermark

PDF & files

  • Merge PDFs
  • Split a PDF
  • Images to PDF
  • PDF to images
  • Remove photo location

Video & audio

  • Compress video
  • Convert video
  • Video to GIF
  • Convert audio
  • Trim audio

Everyday

  • QR codes
  • Passwords
  • Time zones
  • Unit converter
  • Word count
  • Webcam test

Developer

  • JSON formatter
  • Base64
  • Regex tester
  • Hashes
  • JWT decoder

Site

  • About
  • Contact
  • Settings
  • Privacy
  • Terms
  • Site map
  • llms.txt

Everyday

  • Images
  • Video
  • Audio
  • PDF & files
  • Text
  • QR codes
  • Units & math
  • Time & dates
  • Color
  • Passwords & IDs
  • Device tests
  • Sun & moon

For developers

  • JSON
  • Encoding
  • Regex & cron
  • Web & auth
  • Hashing & encryption
  • Config files
  • Network
  • Browser
  • AI
  • Fake data
© Nutter Toolsnutter.tools
  1. Home
  2. Units & math
  3. Motor starting current
Your files stay on your device

Motor starting current

Compare starting current and torque across DOL, star delta, autotransformer, and soft start, with the voltage dip each method causes.

This tool is in beta

Still being tested. If a result looks wrong, tell us.

Report a problem

Enter the motor rating and a supply to compare starting methods.

The locked-rotor current is what the motor draws the instant it is energized, and it does not care how light the load is; it is set by the rotor design, typically 5.5 to 8 times full load for a modern cage motor, which is why NEMA publishes code letters as kVA per horsepower (IEC 60034-12 covers the same duty for IEC motors). Starting kVA is the number that matters to the supply: it sets the voltage dip, and it is what a generator must accept without stalling. Torque falls with the square of the voltage at the motor terminals, so a star-delta starter leaves one third, a 65 percent autotransformer tap leaves 42 percent. One honest caveat: the drive row prices torque with the same voltage-squared rule at line frequency, but a real drive ramps voltage with frequency (constant V/f), so its actual starting torque is far higher than the figure shown; its row is a line-current comparison, not a torque prediction.

Motor and supply

Phase
Locked-rotor currentA motor property, typically 5.5 to 8 times full load for a cage motor
SupplyNetwork fault level, or a generator and its transient reactance
Autotransformer tapTorque carries the tap squared
More settings▾

The soft starter and the drive clamp their own current. When their limit sits above the locked-rotor multiple, the motor never reaches the clamp and the row shows the multiple instead.

Numbers stay within ±1,000,000,000, voltage at least 1 V, full-load current above zero. Code letters A through U carry their band's upper kVA-per-HP figure; letter V is an open band and is refused.