Your files stay on your device Transformer current Turn a transformer kVA rating into primary and secondary full load amps, with ratios, loading table, fault estimate, and inrush band. Enter a kVA rating and both winding voltages. Read the fault figure for what it is: full-load current divided by the per-unit impedance with the supply assumed infinite, so it overestimates. A real study needs the source impedance and motor contribution per IEC 60909 before anyone sets a protection grade. Delta-star vector groups also shift the winding ratio by root-three relative to the line ratio quoted here. Options More unit & math tools - 4-20 mA scaling (/converters/4-20ma-scaling-calculator) - 555 timer calculator (/converters/555-timer-calculator) - Unit converter (/converters/units) All unit & math tools (/converters) Was this tool useful? YesNo Canonical HTML: https://nutter.tools/converters/transformer-current-calculator Markdown version: https://nutter.tools/converters/transformer-current-calculator.md Plain-text version: https://nutter.tools/converters/transformer-current-calculator.txt Agent index: https://nutter.tools/llms.txt