Your files stay on your device Star-Delta starter Size the three contactors and overload relay for a star delta starter, with winding currents and start values against DOL. Enter the nameplate full-load current to size the starter. The sizing rules: main and delta contactors both carry winding current, 57.7 percent of the line figure, so they are sized at 0.58 times full-load current. The star contactor conducts only during starting and is conventionally sized at 33 percent. The overload relay setting here assumes it sits in the windings, where it reads phase current of 0.58 times nameplate; a relay ahead of the starter reads line current and needs the full nameplate figure. In star, each winding sees V over √3, so starting current and starting torque are exactly one third of the direct-on-line values. Star-delta suits loads that start light; a compressor under load or a conveyor under belt tension may never reach changeover speed in star. Options More unit & math tools - 555 timer calculator (/converters/555-timer-calculator) - 4-20 mA scaling (/converters/4-20ma-scaling-calculator) - Unit converter (/converters/units) All unit & math tools (/converters) Was this tool useful? YesNo Canonical HTML: https://nutter.tools/converters/star-delta-starter-calculator Markdown version: https://nutter.tools/converters/star-delta-starter-calculator.md Plain-text version: https://nutter.tools/converters/star-delta-starter-calculator.txt Agent index: https://nutter.tools/llms.txt