Your files stay on your device Motor starting current Compare starting current and torque across DOL, star delta, autotransformer, and soft start, with the voltage dip each method causes. Enter the motor rating and a supply to compare starting methods. The locked-rotor current is what the motor draws the instant it is energized, and it does not care how light the load is; it is set by the rotor design, typically 5.5 to 8 times full load for a modern cage motor, which is why NEMA publishes code letters as kVA per horsepower (IEC 60034-12 covers the same duty for IEC motors). Starting kVA is the number that matters to the supply: it sets the voltage dip, and it is what a generator must accept without stalling. Torque falls with the square of the voltage at the motor terminals, so a star-delta starter leaves one third, a 65 percent autotransformer tap leaves 42 percent. One honest caveat: the drive row prices torque with the same voltage-squared rule at line frequency, but a real drive ramps voltage with frequency (constant V/f), so its actual starting torque is far higher than the figure shown; its row is a line-current comparison, not a torque prediction. Options More unit & math tools - 555 timer calculator (/converters/555-timer-calculator) - 4-20 mA scaling (/converters/4-20ma-scaling-calculator) - Unit converter (/converters/units) All unit & math tools (/converters) Was this tool useful? YesNo Canonical HTML: https://nutter.tools/converters/motor-starting-current-calculator Markdown version: https://nutter.tools/converters/motor-starting-current-calculator.md Plain-text version: https://nutter.tools/converters/motor-starting-current-calculator.txt Agent index: https://nutter.tools/llms.txt