Your files stay on your device Conduit fill calculator Add cables to a conduit, see the fill percent against the limit, and get the smallest conduit that fits with room to spare. NEC mode reads the Chapter 9 Table 4 EMT series with the Table 1 limits: 53 % for one conductor, 31 % for two, 40 % for three or more, earth wires counted. The 600 mm nipple exception (60 %) is not modelled. IEC mode applies the 40 % conduit convention over the nominal IEC sizes with indicative medium-duty internal diameters; real internal bores vary by maker, so treat the IEC result as indicative too, and trunking as a different animal. Fill is not ampacity: nine current-carrying conductors can pass fill and still need a 70 % ampacity adjustment that forces bigger cables which then do not fit. The indicative preset diameters are not for ordering. Options More unit & math tools - 4-20 mA scaling (/converters/4-20ma-scaling-calculator) - 555 timer calculator (/converters/555-timer-calculator) - Unit converter (/converters/units) All unit & math tools (/converters) Was this tool useful? YesNo Canonical HTML: https://nutter.tools/converters/electrical-conduit-fill-calculator Markdown version: https://nutter.tools/converters/electrical-conduit-fill-calculator.md Plain-text version: https://nutter.tools/converters/electrical-conduit-fill-calculator.txt Agent index: https://nutter.tools/llms.txt